KOP-L - Single-phase transformers for the supply of medical rooms

KOP-L

Single-phase isolating transformer according to DIN EN 61558, VDE 0570, part 2-15 as well as DIN VDE 0107/10.94. Shielding winding between primary and secondary winding. In every branch one PTC-resistor wrapped. Connections: Terminals with screwed connection, prepared for safety class II, 50/60 Hz, ta 40°C, dip impregnation.

P: 3,15 - 8,00 kVAUPRI: 230 VUSEC: 115 V

Download data sheet

Product images
Schematics

* according to DIN VDE 0107/10.94 * Impedance voltage: Uk < 3 % * No-load current: I0 < 3 % * Inrush current: max. 12 x IN * PTC resistor for signalling thermal overload. * Static shielding between primary and secondary windings taken to insulated connection terminal. * Secondary winding with middle tapping (115 V - 0 - 115 V) for insulation monitoring. * Test voltage min. 4000 V. * Available in sheet steal casing, type of enclosure IP 23. * Against the core isolated angle brackets


Variants overview

Output Article number Measurements Weight
Rated capacity PRI 230 V
SEC 115 / 0 / 115 V
a x b x c / L x B x HCU kgGes. kg
kVA
3.15 240 x 300 x 2311747
4 240 x 300 x 2461953
5 280 x 350 x 2302762
6.3 280 x 350 x 2452771
8 280 x 350 x 2603788
Request product

Contact us!

Are you still looking for the right product? Contact us now. We work with you to develop the right solution, optimally tailored to your requirements.

VYUŽÍVEJTE NAŠE FILTRY VÝROBKŮ

Váš vhodný transformátor, cívku nebo požadovaný filtr naleznete nejjednodušeji s našimi filtry výrobků. S nastaveními filtru, například vstupního a výstupního napětí nebo stupně krytí IP, zvolíte své individuální parametry a naleznete správný výrobek z našeho rozmanitého sortimentu.

Mimochodem: Také se můžete pomocí kontaktního formuláře dotázat našeho týmu prodeje na individuální nabídky a zákaznicky specifická řešení.

Objevte naše filtry výrobků:

Zvolit transformátory     Zvolit cívky nebo filtry