KOP
Single-phase isolating transformer according to DIN EN 61558, VDE 0570, part 2-15 as well as DIN VDE 0107/10.94. Shielding winding between primary and secondary winding. In every branch one PTC-resistor wrapped. Connections: Terminals with screwed connection, prepared for safety class II, 50/60 Hz, ta 40°C, dip impregnation.
P: 3,15 - 8,00 kVAUPRI: 230 VUSEC: 115 V
Download data sheetVariants overview
| Output | Article number | Measurements | Weight | |
|---|---|---|---|---|
| Rated capacity | PRI 230 V SEC 115 / 0 / 115 V | a x b x c / L x B x H | CU kg | Ges. kg |
| kVA | ||||
| 3.15 | 240 x 184 x 314 | 17 | 47 | |
| 4 | 240 x 199 x 314 | 19 | 53 | |
| 5 | 280 x 199 x 362 | 27 | 62 | |
| 6.3 | 280 x 214 x 362 | 27 | 73 | |
| 8 | 280 x 229 x 362 | 37 | 88 | |